Publication:
Comparison of Core Loss and Magnetic Flux Distribution in Amorphous and Silicon Steel Core Transformers

dc.authorscopusid57209132135
dc.authorscopusid15019302900
dc.contributor.authorNajafi, A.
dc.contributor.authorÏskender, I.
dc.date.accessioned2020-06-21T13:11:07Z
dc.date.available2020-06-21T13:11:07Z
dc.date.issued2018
dc.departmentOndokuz Mayıs Üniversitesien_US
dc.department-temp[Najafi] Atabak, Department of Electrical and Electronic Engineering, Ondokuz Mayis Üniversitesi, Samsun, Turkey; [Ïskender] Ïres, Department of Electrical and Electronic Engineering, Gazi Üniversitesi, Ankara, Ankara, Turkeyen_US
dc.description.abstractNo-load losses are caused by the magnetizing current that needed to energize the transformers core. These losses are constant and occur 24 h a day, regardless of the load. So, the customers should pay the fixed monthly cost for these losses. In recent years, amorphous alloy has been used to improve distribution transformers performance with the decrease in No-load losses and the increase in the efficiency of transformers. This paper outlines the 2605SA1 amorphous core as a new development of the amorphous alloy with a higher saturation induction. This paper presents a comparison between traditional distribution transformers and amorphous distribution transformers. Distribution of flux density in two different transformers with amorphous core and M5-type silicon steel core has been simulated using 3-D finite element modelling. The simulation and modelling results have been compared with the tests results of 630 kVA, 34.5/0.4 kV prototypes manufactured in the TEK TRANSFORMER factory in Turkey. A good agreement has been obtained between the simulation and experimental results. The simulation and test results show that amorphous core considerably (about 63%) reduces the no-load power losses as well as efficiency of transformers. © 2017, Springer-Verlag GmbH Germany.en_US
dc.identifier.doi10.1007/s00202-017-0574-7
dc.identifier.endpage1131en_US
dc.identifier.issn0948-7921
dc.identifier.issn1432-0487
dc.identifier.issue2en_US
dc.identifier.scopus2-s2.0-85020248362
dc.identifier.scopusqualityQ2
dc.identifier.startpage1125en_US
dc.identifier.urihttps://doi.org/10.1007/s00202-017-0574-7
dc.identifier.volume100en_US
dc.identifier.wosWOS:000432411800062
dc.identifier.wosqualityQ3
dc.language.isoenen_US
dc.publisherSpringer Verlag service@springer.deen_US
dc.relation.ispartofElectrical Engineeringen_US
dc.relation.journalElectrical Engineeringen_US
dc.relation.publicationcategoryMakale - Uluslararası Hakemli Dergi - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.subjectAmorphous Coreen_US
dc.subjectDistribution Transformersen_US
dc.subjectFinite Element Methoden_US
dc.subjectMagnetic Materialsen_US
dc.subjectNo-Load Lossesen_US
dc.titleComparison of Core Loss and Magnetic Flux Distribution in Amorphous and Silicon Steel Core Transformersen_US
dc.typeArticleen_US
dspace.entity.typePublication

Files