Publication:
Reduction of Stray Loss on Transformer Tank Wall with Optimized Widthwise Electromagnetic Shunts

dc.contributor.authorNajafi, Atabak
dc.contributor.authorOzgonenel, Okan
dc.contributor.authorKurt, Unal
dc.date.accessioned2020-06-21T13:26:55Z
dc.date.available2020-06-21T13:26:55Z
dc.date.issued2017
dc.departmentOMÜen_US
dc.department-temp[Najafi, Atabak -- Ozgonenel, Okan] Ondokuz Mayis Univ, Elect & Elect Engn, Samsun, Turkey -- [Kurt, Unal] Amasya Univ, Elect & Elect Engn, Amasya, Turkey --en_US
dc.description10th International Conference on Electrical and Electronics Engineering (ELECO) -- NOV 30-DEC 02, 2017 -- Bursa, TURKEYen_US
dc.description.abstractThis paper presents an optimized widthwise electromagnetic shunt as a cost-effective way to reduce the stray losses in transformer tank walls. A 1000 KVA, 10/0.4 kV oil immersed distribution transformer is used. 3-D finite element method (FEM) has been used to analysis and study the impact of proposed magnetic shunt on the reduction of tank losses. In this paper different combinations of optimized magnetic shunt have been studied. The paper compares the performance of proposed optimized magnetic shunt with the available conventional shunts. Considerable reductions in stray losses on the transformer tank wall are obtained by using the combinations of electromagnetic shunt with optimal thickness. Compared with aluminum shields and conventional electromagnetic shunt, the proposed optimized widthwise magnetic shunt reduces stray losses by 13.96%.en_US
dc.description.sponsorshipChamber Elect Engineers Bursa Sect Branch, Uludag Univ, Fac Engn, Dept Elect & Elect Engn, Istanbul Tech Univ, Fac Elect & Elect Engn, Sci & Technolog Res Council Turkey, IEEE Turkey Secten_US
dc.identifier.endpage10en_US
dc.identifier.isbn9781538617236
dc.identifier.startpage6en_US
dc.identifier.urihttps://hdl.handle.net/20.500.12712/12666
dc.identifier.wosWOS:000426978800002
dc.language.isoenen_US
dc.publisherIEEEen_US
dc.relation.journal2017 10Th International Conference on Electrical and Electronics Engineering (Eleco)en_US
dc.relation.publicationcategoryKonferans Öğesi - Uluslararası - Kurum Öğretim Elemanıen_US
dc.rightsinfo:eu-repo/semantics/closedAccessen_US
dc.titleReduction of Stray Loss on Transformer Tank Wall with Optimized Widthwise Electromagnetic Shuntsen_US
dc.typeConference Objecten_US
dspace.entity.typePublication

Files